Submitted by DonHester on Tue, 06/14/2016 - 07:14.
Paint it black- You must be properly Identified.
Wenatchee Home Inspections
This is something I always have wondered about. Quite often when looking at electrical panels we see the white wire (grounded conductor or Neutral) used and an Hot (ungrounded) conductor which is typically black.
This can be done and to be proper the white wire is supposed to be reidentified as an ungrounded conductor, such as marking it black (or any color that is approved for a hot conductor). So often though the white wire never gets re-identified. This was done wrong so often and overlooked that it was commonplace.
White conductors re-identified
So it made me think has it always been this way or was there a time when you did not need to re-identify the white conductor? Turns out it is a bit confusing.
So let’s jump into it, from the NEC 2014 on the use of white or grey color insulation on conductors. (This is pretty similar back to 1999) 200.7 Use of Insulation of a White or Gray Color or with Three Continuous White or Gray Stripes
(C) Circuits of 50 Volts or More.
The use of insulation that is white or gray or that has three continuous white or gray stripes for other than a grounded conductor for circuits of 50 volts or more shall be permitted only as in (1) and (2).
(1) If part of a cable assembly that has the insulation permanently reidentified to indicate its use as an ungrounded conductor by marking tape, painting, or other effective means at its termination and at each location where the conductor is visible and accessible. Identification shall encircle the insulation and shall be a color other than white, gray, or green. If used for single-pole, 3-way or 4-way switch loops, the reidentified conductor with white or gray insulation or three continuous white or gray stripes shall be used only for the supply to the switch, but not as a return conductor from the switch to the outlet.
So you see that they can be used as an ungrounded conductor as long as it is properly re-identified.
From the 2014 NEC Handbook-
Examples of applications where it might be necessary to re-identify and use a white or gray insulated conductor as an ungrounded conductor include water heaters, electric heat, motors, and switch loops. The insulation is re-identified to avoid confusing it with grounded conductors having white or gray insulation or neutral conductors at switch and outlet points and at other points in the wiring system where the conductors are accessible.
In previous editions, the Code permitted switch loops using a white insulated conductor to serve as an ungrounded conductor supplying the switch but not as the return ungrounded conductor to supply the lighting outlet. Prior to the 1999 NEC, re-identification of a white conductor used for this purpose was not required. However, electronic switching devices with small power supplies are available that can be installed at switch locations. These devices require a grounded conductor in order to power the internal components, and they help in clearly distinguishing a grounded conductor from ungrounded conductors, which aids in properly connecting such devices. Although in switch loops, the conductor with white or gray insulation is re-identified at all accessible locations to indicate that it is an ungrounded conductor, it is only permitted to supply the switch and cannot be the switched ungrounded conductor at the controlled outlet.
From New Hampshire document on common code violations-
“A conductor with white or gray insulation that is part of a cable assembly has been used to supply to a single pole switch as part of a single pole switch loop for a luminaire and it has not been reidentified by painting or other effective means (taping) at the point of supply or at the single pole switch. This method of switching luminaires and receptacles has been a common application for many years and prior to 1999 did not require the white or gray conductor to be reidentified. Therefore, this requirement is often overlooked.”
So in 1987 it states at its termination and each location where visible From 1987 NEC 200-7. Use of White or Natural Gray Color. A Continuous white or natural gray covering on a conductor or a termination marking of white or natural gray color shall be used only for the grounded conductor.
Exception No. 1: An insulated conductor with a white or natural gray finish shall be permitted as an ungrounded conductor where permanently re-identified to indicate its use, by painting or other effective means at its termination, and at each location where the conductor is visible and accessible.
Exception No. 2: A cable containing an insulated conductor with a white or natural gray outer finish shall be permitted for single-pole, 3-way, or 4-way switch loops where the white or natural gray conductor is used for the supply to the switch, but not as a return conductor from the switch to the switched outlet. In these applications, re-identification of the white or natural gray conductor shall not be required.
In 1975 it states at its termination and and at each outlet where the conductor is visible and accessible.
From 1975 NEC
200-7. Use of White or Natural Gray Color. A Continuous white or natural gray covering on a conductor or a termination marking of white or natural gray color shall be used only for the grounded conductor.
Exception No. 1: An insulated conductor with a white or natural gray finish shall be permitted as an ungrounded conductor where permanently re-identified to indicate its use, by painting or other effective means at its termination, and at each outlet where the conductor is visible and accessible.
Exception No. 2: A cable containing an insulated conductor with a white or natural gray outer finish shall be permitted for single-pole, 3-way, or 4-way switch loops where the white or natural gray conductor is used for the supply to the switch, but not as a return conductor from the switch to the switched outlet. In these applications, re-identification of the white or natural gray conductor shall not be required.
In 1959 is says where visible and accessible From 1959 NEC
200-7. Identified Conductors in Grounded Circuits Only. Conductors having white or natural gray covering shall not be used other than as conductors for which identification is required by Section 200-2, except under the following conditions, and then only where they are, in other respects, suitable for use as ungrounded conductors in a circuit:
Exception No. 1: Identified conductor, rendered permanently unidentified by painting or other effective means at each outlet where the conductors are visible and accessible, may be used as unidentified conductors.
Exception No. 2: Cable containing an identified conductor may be used for single-pole, three-way, or four-way switch loops where the connections are so made that the unidentified conductor is the return conductor from the switch to the outlet.
white or natural gray conductor is used for the supply to the switch, but not as a return conductor from the switch to the switched outlet. In these applications, re-identification of the white or natural gray conductor shall not be required.
This is the requirement but when did this all start? Well it turns out this is not a new requirement and doing a little history search I found this requirement goes back quite a ways, to at least as early as 1933 (as early as I could find it).
From the 1933 National Board of Fire Underwriters -
1933 "NATIONAL ELECTRICAL CODE"
REGULATIONS OF THE
National Board of Fire Underwriters
FOR
ELECTRIC WIRING
AND
APPARATUS
AMERICAN STANDARD
Approved September 1, 1933
NBFU-70 1933
2001. Polarity Identification of Systems and Circuits.
e. The polarized grounded wire of an interior wiring system shall be continuously identified
throughout the system by the use of an identified outer covering, as specified in paragraph F of section 602 of Article 6 of this code, for rubber covered wires No. 6 and smaller. For larger wires and wires of other than rubber-covering the identification shall be secured either with the white or natural grey outer covering, or by a distinctive marking at terminals during the process of installation.
f. Wires having white or natural grey covering shall not be used in identified systems or circuits other than as conductors for which identification is required by this section, unless the identified wire is rendered permanently unidentified by painting or other effective means at every outlet where the wires are visible and accessible, except that single-pole switch loops in circuits wired with armored cable, or with non-metallic sheathed cable may contain a white or natural grey conductor if the connections are so made that the return conductor from the switch to the outlet is black or a color other than white or natural grey.
So as you can see this goes back quite a ways and covers the vast majority of homes.
“I like light, color, luminosity. I like things full of color and vibrant. “
Oscar de la Renta
If you find any errors or have additional information that would expand on any code, building standards or manufacturer requirements please let me know.
NCW Home Inspections, LLC is a Licensed Washington State Home Inspection service located in Wenatchee Washington serving Chelan County, Douglas County, Kittitas County, Okanogan County and Grant County Washington and the cities of Wenatchee, Leavenworth, Cashmere, Oroville, Cle Elum, East Wenatchee, Quincy and many more…
Your Wenatchee and Chelan Professional Real Estate, Home and Structural Pest Inspection Service
Instructor- Fundamentals of Home Inspection- Bellingham Technical College
If you find any errors or have additional information that would expand on any code, building standards or manufacture requirements please let me know.